CT-Circulating Water Analysis

Parameters Control Limit
pH 8.1-8.3
TDS <1625
Cond (mmhos) <2500
Total Hardness <850
T.ALK <300
Chlorides(ppm) <300
OPO4(ppm) 5 to 8
IRON <3
ZINC 1 to 2
Silica(ppm) <160
Turbidity <20
COC - RAW 7 to 8
ORP 350 To 400
COC-RO
Calcium hardness
SSF-IN-Turbidity -
SSF-OUT-Turbidity
RW Make-up(M3)
RO Make-up(M3)
TSS
P3 P33 P32 N.FMP N-P-14 N-P-17 N-P-3
7.5 8.6 7.7 7 7 7 7
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0.00 0.00 0.00 0.00 0.00 0.00 0.00
CT Name Remark
P3 All parameter are within desired limits.
P33 All parameter are within desired limits.
P-32 All parameter are within desired limits.
N.FMP Turbidity is running higher side in C/T, request you to give SSF back wash and bottom blow down.
N-P-14 TDS, Conductivity,Chloride & Turbidity is running higher side in C/T, request you to give SSF back wash and bottom blow down.
N-P-17 All parameter are within desired limits.
N-P-3 TDS, Conductivity & Turbidity is running higher side in C/T, request you to give SSF back wash and bottom blow down.
MPP-2/P-17 All parameter are within desired limits.
RO Permit Water Chloride is on higher side.
Raw Water Value All parameter are within desired limits.