CT-Circulating Water Analysis
Parameters | Control Limit |
---|---|
pH | 8.1-8.3 |
TDS | <1625 |
Cond (mmhos) | <2500 |
Total Hardness | <850 |
T.ALK | <300 |
Chlorides(ppm) | <300 |
OPO4(ppm) | 5 to 8 |
IRON | <3 |
ZINC | 1 to 2 |
Silica(ppm) | <160 |
Turbidity | <20 |
COC - RAW | 7 to 8 |
ORP | 350 To 400 |
COC-RO | |
Calcium hardness | |
SSF-IN-Turbidity | - |
SSF-OUT-Turbidity | |
RW Make-up(M3) | |
RO Make-up(M3) | |
TSS |
P3 | P33 | P32 | N.FMP | N-P-14 | N-P-17 | N-P-3 |
---|---|---|---|---|---|---|
7.5 | 8.6 | 7.7 | 7 | 7 | 7 | 7 |
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
1 | ||||||
0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CT Name | Remark |
---|---|
P3 | All parameter are within desired limits. |
P33 | All parameter are within desired limits. |
P-32 | All parameter are within desired limits. |
N.FMP | Turbidity is running higher side in C/T, request you to give SSF back wash and bottom blow down. |
N-P-14 | TDS, Conductivity,Chloride & Turbidity is running higher side in C/T, request you to give SSF back wash and bottom blow down. |
N-P-17 | All parameter are within desired limits. |
N-P-3 | TDS, Conductivity & Turbidity is running higher side in C/T, request you to give SSF back wash and bottom blow down. |
MPP-2/P-17 | All parameter are within desired limits. |
RO Permit Water | Chloride is on higher side. |
Raw Water Value | All parameter are within desired limits. |